A. General Electrical & Transformer Fundamentals
Basic concepts that sales, project and service teams are most often asked about when discussing power equipment with customers.
Q1: What is a transformer?
A: A transformer is a static (stationary) electrical device that, based on the principle of electromagnetic induction, exchanges and transfers electromagnetic energy between two or more winding circuits linked to a common magnetic core. It changes voltage and current levels while keeping the frequency unchanged, which makes it the key equipment for power transmission, distribution and utilisation.
Q2: What is a single-phase transformer and how does it work?
A: A single-phase transformer is a transformer operated from a single-phase AC supply, that is, from one alternating voltage. Its two principal windings are:
• Primary winding - connected directly to the power source.
• Secondary winding - connected to the load or to the device requiring voltage regulation.
Working principle: when an alternating current flows through the primary winding it generates an alternating magnetic field in the core. This field is conducted through the core to the secondary winding and, according to Faraday's law of electromagnetic induction, induces an electromotive force in it. The ratio of the primary and secondary voltages equals the ratio of the number of turns, which determines whether the unit works as a step-up transformer (raises voltage) or a step-down transformer (lowers voltage).
Q3: What are the main components of a transformer?
A: • Core - built from laminated silicon steel to minimise energy loss.
• Primary winding - receives the input power.
• Secondary winding - delivers the output power.
• Insulation - prevents short circuits between windings, turns and earth.
• Tank / enclosure - protects the internal components and, in oil-filled designs, holds the cooling oil.
Q4: What are the main types of single-phase transformers and where are they used?
A: Main types:
• Step-up transformer - increases the voltage from the primary side to the secondary side.
• Step-down transformer - reduces the voltage from the primary side to the secondary side.
• Isolation transformer - provides electrical isolation at the same voltage level.
Typical applications:
• Residential and commercial power supply.
• Lighting systems in public and private spaces.
• HVAC (heating, ventilation and air-conditioning) systems.
• Small industrial equipment with lower voltage requirements.
• Electronic devices requiring a stable supply voltage.
Q5: Why do power systems use 50 Hz?
A: The choice of 50 Hz results from a combination of historical and technical reasons - essentially a compromise between motor efficiency, transmission losses and the suitability of the frequency for steam-turbine generators:
• Lower core losses - at 50 Hz, transformers and other magnetic equipment show lower core losses than at 60 Hz, giving higher efficiency and less heat.
• Longer equipment life - the lower frequency reduces electrical and mechanical stress on equipment.
• Efficient motors - motors designed for 50 Hz can be more efficient for the same output.
• Long-distance transmission - lower line losses make 50 Hz better suited to long-distance power transmission.
• Lower corona loss - the energy dissipated by the hissing and violet glow around high-voltage conductors is lower at 50 Hz.
Note: 60 Hz is standard in North America and in a few other regions. Tianrun transformers can be designed and manufactured for either 50 Hz or 60 Hz - the required frequency must be stated in the order.
Q6: What are active power, reactive power and power factor?
A: Active power (P) is the power actually converted into mechanical, thermal or light energy and used to do useful work. Unit: watt (W) or kilowatt (kW). Active power must be balanced with demand in real time: a deficit causes the system frequency to drop (in severe cases leading to equipment shutdown or grid collapse), while a surplus raises the frequency and equally endangers equipment.
Reactive power (Q) is the power exchanged between the electric and magnetic fields of a circuit. It performs no external work but is indispensable for establishing the magnetic fields that transformers and motors need in order to operate. Unit: var or kvar. Reactive power directly influences the grid voltage: a shortage causes the line voltage to fall (particularly on long lines), while an excess causes it to rise.
Power factor (PF) is the ratio of active power to apparent power: PF = P / S, ranging from 0 to 1. The closer the power factor is to 1, the higher the utilisation of electrical energy and the lower the additional losses in lines and equipment. A low power factor increases line current and line losses and reduces the usable active output of generators and transformers, which is why grids normally require a high power factor, achieved if necessary by capacitive compensation.
Note: In short: active power is the "energy that does work" and governs frequency; reactive power is the "energy that builds the magnetic field" and governs voltage; power factor is the "yardstick of efficiency".
Q7: What is the neutral point in a power network, and how is it earthed?
A: The neutral point of a power network is the neutral point of a star-connected transformer or generator. Its earthing methods fall into two main categories:
• Direct earthing of the neutral point.
• Non-earthing of the neutral point, or earthing through an arc-suppression (Petersen) coil.
In a neutral-point earthing complete set of equipment, the two earthing methods are selected by opening or closing the earthing switch. During normal operation the neutral-point voltage is close to 0 V, but asymmetric faults or three-phase unbalance give it a certain value, so a lightning arrester is installed to protect against over-voltage.
Two metal rods placed together form an air gap for lightning protection: when a lightning surge arrives or the neutral-point voltage becomes too high, the air gap discharges, which is equivalent to connecting that point to earth. The single-phase current transformer measures the current flowing from the neutral point to earth.
Q8: What is a cable?
A: A cable is an essential component of electrical and electronic systems, used to transmit electricity or signals from one place to another. It is usually made up of several thin conductive cores, each insulated and protected by an outer sheath. Note that a single conductor on its own is not a complete cable.
Cables are classified by application as follows:
• Power cables - transmit electrical energy from generation sources to residential, commercial and industrial facilities.
• Communication cables - carry data, audio and video signals for telecommunications, internet and optical-fibre systems.
• Control cables - transmit control signals in automation and instrumentation systems.
• Radio-frequency (RF) cables - carry high-frequency signals for wireless communication, broadcasting and surveillance.
They can also be classified by conductor material (copper or aluminium), by insulation material (rubber, oil-impregnated paper or plastic) and by number of cores (single, double, three or multi-core).
Q9: What is a main transformer (main substation transformer)?
A: The main transformer converts the electrical energy generated at power plants, by stepping the voltage up or down, into low-voltage energy suitable for transmission, distribution and end use. It works on electromagnetic induction: an alternating current in the high-voltage winding creates an alternating magnetic field, which is conducted through the core to the low-voltage winding and induces an electromotive force there.
Main components: core assembly (core, windings, leads and insulation), tank and cover (with oil sampling valves, drain plugs, earthing bolts, etc.), protective devices (conservator, oil level gauge, oil purifier, flow relay, desiccant breather, signal thermometer), cooling system and outlet bushings.
Applications: the three fields of the power system - transmission, distribution and consumption - as well as industry, construction and residential areas, e.g. power machinery, welding and arc furnaces, power supply and distribution, and indoor lighting.
Q10: What is a box-type substation?
A: Strictly speaking, the term "box-type substation" (often shortened to "box sub") refers to a compact, prefabricated substation. It integrates high-voltage power reception, transformer step-down and low-voltage distribution in one moisture-proof, rust-proof, dust-proof, rodent-proof, fire-proof, theft-proof, heat-insulated, fully enclosed and movable steel enclosure.
Classification:
• By appearance and material: wooden, stone and steel-shell box substations.
• By structure: combined type (American style) and prefabricated type (European style).
• American style is further divided into common-tank and separate-tank designs according to the tank structure; European style is divided into ring-main and terminal types.
Features: compact structure (transformer, HV and LV switchgear and protection devices in one enclosure, small footprint, easy transport and installation); high safety (fully enclosed, protected from animals and moist air, complete internal protection); high flexibility (customised capacity, voltage level and configuration, and mobile supply for temporary or emergency use).
Structure: generally composed of a high-voltage room, a transformer room and a low-voltage room, arranged either in a "T" (pin) layout or a "square" (mu) layout.
Applications: residential communities, industrial parks, shopping malls and similar locations, combining appearance with practicality.
Q11: What is the difference between a main transformer and a box-type substation?
A: See the comparison table below:
|
Item |
Main transformer |
Box-type substation |
|
Rated capacity |
Generally 1000 kVA and above |
Typically 10 - 630 kVA |
|
Application |
Medium and large grids, power stations and other large facilities; steps voltage up or down to keep the grid at the intended value |
Residential areas, industrial parks and shopping malls; steps the HV grid voltage down to LV for safe, convenient supply |
|
Reliability requirement |
High - critical to the power system |
Moderate - lower than for the main transformer |
|
Design |
Larger and heavier, requiring a large installation area; consists of the transformer body, cooling equipment, incoming and outgoing lines |
Much smaller, box-type design for fast installation in urban areas or communities |
B. Dry-Type Transformer: Basics, Types & Selection
Core knowledge on epoxy resin cast dry-type transformers - the company's principal product line - including how they compare with oil-immersed units and how to select the right model.
Q1: What are the characteristics and market prospects of dry-type transformers?
A: Dry-type transformer products are safe, flame-retardant, fire-resistant and pollution-free. They can be installed directly at the load centre, are maintenance-free, easy to install and have low overall operating cost. Their main characteristics are:
• Excellent moisture resistance - they operate normally at 100% humidity and can be returned to service without pre-drying after a shutdown.
• Low losses, low partial discharge and low noise.
• Strong heat dissipation - up to 150% of rated load under forced-air cooling (AF).
• A complete temperature protection and control system that reliably safeguards operation.
Because of these advantages, dry-type transformers are increasingly specified for high-density urban areas, commercial buildings, data centres, hospitals, rail transit and other places with stringent fire-safety requirements.
Q2: What is the difference between dry-type and oil-immersed transformers?
A: See the comparison table below:
|
Item |
Dry-type transformer |
Oil-immersed transformer |
|
Cooling method |
Natural air cooling (AN) or forced-air cooling (AF) |
Oil circulation cooling |
|
Heat dissipation |
Air-duct dissipation |
Oil-duct dissipation; every unit requires an oil tank |
|
Safety |
Safe, flame-retardant, fire-resistant, non-polluting; can be installed directly at the load centre |
Flammable and not fire-proof; causes a certain amount of pollution |
|
Maintenance |
Maintenance-free, simple installation, low overall cost |
Requires frequent maintenance |
|
Moisture resistance |
Operates normally at 100% humidity; can be energised immediately after shutdown without pre-drying |
Requires drying and regular oil treatment |
|
Typical application |
Areas with high population density and strict fire-protection requirements |
Open outdoor substations where fire risk is less critical |
Q3: How should a customer choose the right transformer?
A: If the lowest initial purchase price is the only consideration, an oil-immersed transformer may be considered. If safe operation, maintenance cost and environmental protection are taken into account, a dry-type transformer is recommended. In practice the decision should weigh total cost of ownership - installation space, fire protection, maintenance and operating losses - rather than purchase price alone.
Q4: What components make up a dry-type transformer?
A: • Core
• Windings
• Fastening and supporting parts
• Leads
• Insulation
• Cooling device - temperature controller and fan
• Protective device - transformer enclosure
Q5: What are the main product categories of dry-type transformers?
A: • Dry-type power transformers
• Distribution transformers
• Traction rectifier transformers
• Special dry-type transformers such as grounding transformers and arc-suppression coils
• Non-standard (customised) dry-type transformers
• Dry-type reactors
Q6: What are the differences among the four common manufacturing processes: SC, SC(L)B, SG and SCR?
A: See the comparison table below:
|
Item |
SC |
SC(L)B |
SG |
SCR |
|
Process |
Both HV and LV windings of copper wire, vacuum epoxy casting |
HV winding of copper wire, LV winding of copper (aluminium) foil, vacuum epoxy casting |
Epoxy resin impregnation, no casting |
Wound type, no impregnation and no casting |
|
Advantages |
Lower cost |
Good short-circuit and lightning-impulse withstand; good heat dissipation |
Lower cost; winding material recyclable |
Thermal insulation class H |
|
Disadvantages |
Poor short-circuit and lightning-impulse withstand |
Higher cost |
Poor short-circuit and lightning-impulse withstand |
Poor short-circuit and lightning-impulse withstand |
Note: Tianrun's mainstream products adopt the SC(L)B process: epoxy resin vacuum casting with a foil-wound low-voltage winding, which offers the best overall balance of safety, short-circuit strength and service life.
Q7: What is the difference between SC(L)B and SC?
A: 1) Coil winding
• SC(L)B: the LV coil is foil-wound - single- or double-layer copper (aluminium) foil, with epoxy resin containing a latent curing agent and F-class composite foil (DMD paper) between layers; the conductor is oxygen-free copper of 99.99% purity for excellent conductivity.
• SC: the LV coil is wire-wound - a cylindrical coil made of several glass-fibre-insulated flat copper wires wound in parallel.
2) Resistance to sudden short-circuit
• SC(L)B: the reactance height equals the winding height, the same as for the HV coil, so the axial short-circuit force generated under a sudden short circuit is relatively small. Because the whole winding is a single wide, thin foil, it strongly resists axial tensile rupture.
• SC: multiple parallel conductors give a very large end helix angle and a strong end leakage field, producing a very large short-circuit force; unless the structure is adequately reinforced, axial damage is likely.
3) Low-voltage temperature rise - the LV winding is close to the core and dissipates heat with difficulty. The SC(L)B foil structure allows ventilation surfaces to be arranged conveniently and air flow to be increased, so the LV temperature rise is on average 5 - 7 K lower than for a wire-wound structure, improving overload capability and service life.
4) Load loss - for the same voltage class and rating, the SC(L)B foil structure reduces skin-effect additional losses by an average of 5% compared with SC.
5) Insulation performance - in the SC(L)B foil structure the voltage gradient between layers of the LV winding is very low, giving higher dielectric strength; the larger turn-to-turn capacitance also improves withstand of over-voltages and lightning impulses.
Q8: What insulation structures are commonly used for resin-insulated dry-type transformers?
A: • Thin insulation structure with epoxy resin casting (thin-insulation type);
• Epoxy resin wound structure (wound type);
• Thick insulation structure cast with filled epoxy resin (filled type);
• Vacuum impregnation structure (open type).
Q9: How is a dry-type transformer model designated? What does SCZB9-1000/10 mean?
A: Model designation: SC (B) (Z) 10 - XXXX / *
|
Code position |
Meaning |
|
S |
Three-phase |
|
C |
Solid, moulded insulation (epoxy resin casting) |
|
B |
Low-voltage foil-wound coil |
|
Z |
On-load tap-changing |
|
10 |
Performance level code (e.g. 9, 10, 11, 12, 13) |
|
XXXX |
Rated capacity (kVA) |
|
* |
Rated high-voltage voltage class (kV) |
SCZB9-1000/10 therefore means: a three-phase dry-type on-load tap-changing transformer with a rated capacity of 1000 kVA; the HV winding is wire-wound at a voltage class of 10 kV and the LV winding is foil-wound at 0.4 kV.
Q10: What is the difference between Type 9 and Type 10 products?
A: • Type 9: no-load and load losses comply with GB/T 10228-2008.
• Type 10: no-load loss is on average 10% lower than Type 9, and load loss on average 5% lower than Type 9.
Q11: What are the main manufacturing processes for dry-type transformers?
A: • Coil winding process;
• Core production process;
• Assembly process.
C. Design, Materials & Manufacturing Process
Details of core structure, materials, insulation systems and the casting process - the questions customers ask when comparing manufacturing quality between suppliers.
Q1: How is the core of a dry-type transformer structured?
A: See the comparison table below:
|
Part |
Contents |
|
Core body |
Magnetic conductor, made of silicon steel sheets |
|
Fastening components |
Clamping pieces, bolts, glass binding tapes, spacers, foot pads, etc. |
|
Insulating components |
Clamping insulation, insulators, insulating tubes, grounding sheets, etc. |
Q2: What do 30, Q and 130 mean in the silicon steel grade 30Q130?
A: • 30 - the silicon steel sheet thickness is 0.30 mm;
• Q - cold-rolled grain-oriented silicon steel;
• 130 - the maximum specific iron loss, P17/50 = 1.30 W/kg.
Q3: What are the common widths and maximum thicknesses of copper and aluminium foil?
A: • Copper foil: common width 600 - 1000 mm, maximum thickness 2 mm.
• Aluminium foil: common width 600 - 1200 mm, maximum thickness 2 mm.
Q4: What is the insulation class of a dry-type transformer, and what is the maximum temperature rise?
A: Tianrun dry-type transformers are generally Class F, with an insulation system temperature of 155 °C. The maximum temperature rise at Class F is 100 K, which leaves a comfortable margin for overload operation and long service life.
Q5: Why is the epoxy casting performed from bottom to top, and why are heating and vacuum applied?
A: Casting from bottom to top ensures that the resin fully penetrates the interior of the insulating materials and completely covers the coils. Heating and vacuum evacuation fully degas the casting resin, preventing bubbles and guaranteeing casting quality. The casting tank can reach a vacuum of 0.2 mbar.
Q6: Which five components are needed when casting coils?
A: • Epoxy resin;
• Curing agent;
• Plasticiser;
• Accelerator;
• Colour paste.
For a filled resin system, a filler such as SiO2 is also required.
Q7: What are a wound-core transformer and an amorphous-alloy transformer?
A: • A wound-core transformer is one whose core is made from a core roll produced on a special winding machine.
• An amorphous-alloy transformer is one whose core is made of amorphous (non-crystalline) alloy material, giving a very low no-load loss.
Q8: What are the advantages of Tianrun's manufacturing process compared with other manufacturers?
A: Tianrun uses a German JORG core cross-cutting line to produce the core. It offers high shearing accuracy, small burrs, multi-head feeding, automatic stacking and step-lap stacking. This reduces the number of times the sheets are vibrated and preserves the intact grain structure of the silicon steel, which lowers no-load loss and noise.
Q9: How does Tianrun reduce the noise of its dry-type transformers?
A: • Design - adjust the core proportion factor to avoid resonance frequencies;
• Materials - use high-quality silicon steel sheet to reduce magnetostriction;
• Processing - advanced core production lines keep burrs below 0.03 mm;
• Assembly - advanced five-step lamination technology minimises core joint air gaps.
At site level, two further measures are effective: erecting sound-insulation walls around the transformer, which significantly lowers the sound level; and process measures such as stepped core joints, bonding the sheared edges with resin varnish after stacking, binding and coating the core limbs with fixing varnish, and using silicone rubber pads at component connections for vibration damping.
Q10: How does Tianrun reduce transformer losses?
A: Through optimised design, selection of high-quality materials and continuous improvement of processing and manufacturing techniques.
D. Performance, Testing, Operation & Maintenance
Testing requirements, protection functions and the operating conditions that determine reliability and service life.
Q1: What are the 8 factory tests and the 2 routine (type) tests for dry-type transformers?
A: The 8 factory (routine) tests are:
• Ratio measurement;
• DC resistance measurement;
• Insulation resistance measurement;
• Power-frequency withstand voltage test;
• Induced withstand voltage test;
• No-load current and no-load loss measurement;
• Load loss measurement;
• Partial discharge measurement.
The 2 type tests are: lightning impulse test and temperature-rise test.
Q2: Which tests must be carried out on site before energising?
A: • DC resistance measurement;
• Ratio measurement;
• Power-frequency withstand voltage test.
Q3: What is partial discharge and how does it affect a dry-type transformer?
A: Partial discharge is discharge that occurs only at a local position of the insulation and does not immediately form a complete breakdown or flashover through the whole insulation. Its hazards are twofold:
• Direct bombardment of the insulation at the discharge point causes local damage that gradually extends until the insulation breaks down;
• The heat, ozone, nitrogen oxides and other active gases produced by the discharge corrode the local insulation, increase its conductivity and eventually cause thermal breakdown.
Q4: What is a sudden short-circuit test and what are the serious consequences?
A: A sudden short-circuit test is a simulation of the most severe fault a transformer may experience in service. The very large short-circuit current causes high losses, rapid heating of the windings and a sharp temperature rise; over a longer time this inflicts severe thermal damage. At the same time the electromagnetic forces acting on the transformer are very large and destroy the dynamic stability of the active part, cracking the coils.
Q5: What is the overload capacity of a dry-type transformer?
A: It is the length of time for which the transformer can operate continuously under conditions exceeding its rated load. With forced-air cooling (AF) a dry-type transformer can run at up to 150% of rated load, and the foil-wound LV design (lower temperature rise) further improves overload capability.
Q6: Which parameter determines the service life of a dry-type transformer, and how is it controlled?
A: Temperature. It is controlled by forced-air cooling and by reducing the load. Keeping the winding hot-spot temperature within the limits of the insulation class (Class F, 155 °C) is the single most effective way to ensure a long service life.
Q7: What are the functions of the temperature controller, the enclosure and the fan?
A: • Temperature controller - performs three-phase temperature scanning, controls the start and stop of the cooling fans (80 °C / 100 °C), issues an over-temperature alarm (130 °C) and an over-temperature trip (150 °C), and can transmit signals remotely to a computer terminal.
• Enclosure - prevents people and foreign objects from approaching the transformer while it is energised, avoiding danger.
• Fan - increases air flow to reduce the temperature rise caused by operating losses, ensuring continuous normal operation.
Q8: What conditions must be met before products may operate in parallel?
A: • The connection (vector) groups are identical;
• The rated voltage ratios are identical;
• The rated impedance voltages are identical (a deviation of ±10% is permitted).
Q9: What is the difference between Dyn11 and Yyn0, and what are their advantages?
A: Yyn0 has a star-connected HV winding and a star-connected LV winding with the neutral point brought out. Dyn11 has a delta-connected HV winding and a star-connected LV winding with the neutral point brought out.
• Dyn11 eliminates the third-harmonic voltage; because the primary side is delta-connected, the secondary neutral point is stable and can be earthed. It is the preferred connection for distribution transformers.
• Yyn0 is usually used for small-capacity transformers. For large capacities it is not recommended because of the high eddy-current losses in metal structural parts.
Q10: Can products of the same capacity but rated 6 kV, 10 kV and 10.5 kV be used interchangeably?
A: No. Their rated voltages and rated transformation ratios are different, so they cannot replace one another. The correct rated voltage must always be confirmed before ordering.
Q11: How is the output voltage of a dry-type transformer regulated?
A: By means of off-circuit (or on-load) tap links on the HV winding. Taking a rated HV of 10 000 ± 2 x 2.5% V as an example, the tap positions correspond to 10 500 V, 10 000 V and 9 500 V. For models with on-load tap-changing (code Z), the tap can be changed under load.
Q12: How can arcing or discharge when a product is energised be resolved?
A: Before energising, thoroughly clean the active part of the transformer and carry out insulation measurement. Dust, moisture or foreign objects on the insulation surface are the most common causes of arcing and discharge at commissioning.
E. Ordering, Installation & Customisation
The information required in a contract, standard configurations and the reason why customised products differ in price and lead time.
Q1: Which technical parameters must be clearly specified in a purchase contract?
A: • Rated capacity (kVA);
• Voltage ratio (kV);
• Short-circuit impedance (Uk %);
• Load loss and no-load loss (or the performance level code);
• Connection (vector) group;
• No-load current;
• Insulation level;
• Protection grade (IP code);
• Frequency (50 Hz / 60 Hz);
• Service conditions (altitude, ambient temperature);
• Cooling method (AN / AF);
• Cable entry and exit arrangement, and accessories.
Q2: Could you give an example of a completed order specification?
A: Example: a customer orders a standard SCB10-2000/10/0.4, Dyn11, Uk = 6%.
|
Item |
Specification |
|
Transformer model |
SCB10-2000/10/0.4 |
|
Rated capacity |
2000 kVA |
|
Rated voltage (primary / secondary) |
10 / 0.4 kV |
|
Connection group |
Dyn11 (alternatives: Yyn0, Dyn1) |
|
Short-circuit impedance |
Uk = 6% |
|
Frequency |
50 Hz (alternative: 60 Hz) |
|
Insulation level |
LI 75 AC 35 / LI 0 AC 3 kV |
|
Service conditions |
Altitude below 1000 m; ambient temperature 25 °C |
|
Cooling method |
AN / AF |
|
Enclosure protection grade |
IP20 (options: IP00, IP30) |
|
Cable entry / exit |
Bottom-in top-out (options: bottom-in side-out, bottom-in bottom-out, top-in side-out) |
|
Accessories |
Temperature controller, cooling fans (other options: zero-sequence CT) |
Q3: What cable entry and exit arrangements are available?
A: • Bottom-in bottom-out
• Bottom-in top-out
• Bottom-in side-out
• Top-in top-out
• Top-in bottom-out
• Top-in side-out
• Side-in side-out
• Side-in bottom-out
• Side-in top-out
Q4: What is a standard horizontal side-outlet busbar, and what is a standard vertical side-outlet busbar?
A: • Standard horizontal side outlet - the outgoing busbar is arranged parallel to the transformer.
• Standard vertical side outlet - the outgoing busbar is arranged perpendicular to the transformer.
Q5: Why are non-standard products more expensive and produced over a longer cycle?
A: • A non-standard product requires redesign of the transformer body and of the moulds, adding a design cycle and a mould production cycle as well as tooling cost and new-product development cost.
• Most non-standard products also need higher-cost materials - for example, reinforced insulation for high-altitude applications.
Q6: What should be checked before the equipment is put into service?
A: • Clean the active part thoroughly and carry out insulation measurement (see D12);
• Carry out the on-site tests listed in D2: DC resistance, ratio and power-frequency withstand voltage;
• Verify the temperature controller settings (fan 80 °C / 100 °C, alarm 130 °C, trip 150 °C);
• Confirm the enclosure protection grade, earthing and cable connections.
F. Standards, Codes & Certification
An overview of the IEC system that governs electrical equipment, and how it relates to national standards and certification.
Q1: How many IEC standards are there, and what areas do they cover?
A: IEC (International Electrotechnical Commission) currently has 89 technical committees (TC) and 107 sub-committees (SC) and has developed thousands of international standards covering electrical, electronic and related technologies. By the end of 2000 IEC had already published 4 885 international standards, and the number is considerably larger today.
Major technical committees and their core standards:
|
Technical committee |
Core standards |
Application fields |
|
TC 57 - Power system control and communication |
IEC 61850 (substation communication); IEC 60870-5 series (telecontrol) |
Smart grid, substation automation, power dispatching, telecontrol |
|
TC 77 - Electromagnetic compatibility (EMC) |
IEC 61000 series |
All electronic and electrical equipment |
|
TC 64 - Electrical installations and protection against electric shock |
IEC 60364 |
Safety of electrical installations in buildings |
|
TC 34 - Lamps and related equipment |
IEC 60598 (luminaires), IEC 62031 (LED modules) |
General, automotive and special-environment lighting |
|
TC 61 - Safety of household and similar appliances |
IEC 60335 series |
Household and commercial appliance safety |
|
TC 62 - Medical electrical equipment |
IEC 60601 series |
Safety and performance of medical diagnostic, therapeutic and monitoring equipment |
|
TC 82 - Solar photovoltaic energy systems |
IEC 61215, IEC 61730 |
Design, safety and performance of PV modules, systems and components |
|
TC 88 - Wind energy generation systems |
IEC 61400 series |
Design, testing, safety and performance of wind turbines |
|
TC 65 - Industrial process measurement, control and automation |
IEC 61131, IEC 61508, IEC 62443 |
Industrial automation, functional safety, industrial control system cyber-security |
|
TC 100 - Audio, video and multimedia systems |
IEC 62368-1 |
Audio, video, IT and communication technology equipment |
|
TC 47 - Semiconductor devices |
IEC 60747 series |
Discrete semiconductor devices and integrated circuits |
Q2: What is the IP protection code?
A: The familiar "IP protection grade" is defined by IEC 60529. It specifies the degree of protection provided by an enclosure against the ingress of solid foreign objects (including dust) and liquids (water). It is used very widely:
• Consumer electronics - e.g. IP68 for mobile phones and watches;
• Industrial equipment - e.g. mining machinery that must exclude dust, water or corrosive liquids;
• Outdoor facilities - outdoor luminaires, typically IP65, exposed to wind, rain and sand;
• Medical equipment - devices that may be cleaned and disinfected must exclude liquids.
Note: For dry-type transformers, common enclosure grades are IP00 (no enclosure), IP20 (standard indoor enclosure) and IP30; higher grades are available on request.
Q3: How is the IEC standards system applied in practice?
A: • Direct adoption - some countries or regions adopt IEC standards directly as national standards.
• Modified adoption - more commonly, countries slightly modify IEC standards or adopt them as equivalent, converting them into their own national standards (for example China's GB standards).
• Conformity assessment - IEC itself does not certify, but it has established three conformity assessment systems: IECEE (CB Scheme, mutual recognition of safety testing and certification), IECEx (certification for explosive atmospheres) and IECQ (quality assessment of electronic components).
Companies normally contact the national standards body or an authorised certification body to obtain standard texts and to arrange product testing and certification.
Q4: Into which categories are IEC standards grouped by subject?
A: • Basic standards - terminology, units and symbols, graphical symbols, terminal markings, standard voltages, current ratings and frequencies, insulation coordination, insulation systems;
• Raw material standards - working fluids for electrical instruments, insulating materials, measurement methods for electrical properties of metals;
• General safety, installation and operation standards - electrical installations in buildings and in severe outdoor conditions, equipment for explosive gas atmospheres, electrical equipment in industrial machines, enclosure protection, live-working tools;
• Measurement, control and general testing standards - energy measurement and load control, measurement of basic electrical quantities, industrial process measurement and control, nuclear instrumentation, instrument transformers, high-voltage test techniques;
• Power generation and utilisation standards - rotating machines, steam turbines, transformers, power capacitors, relays, photovoltaic systems, electric traction, welding, electro-heating, electric vehicles;
• Power transmission and distribution standards - switchgear and controlgear, wires, low- and high-voltage fuses, surge arresters, telecontrol, protection and communication equipment;
• Electronic component and assembly standards - semiconductor devices and integrated circuits, capacitors and resistors, miniature fuses, cables, electromechanical components, magnetic components;
• Telecommunication, electronic system, IT standards - radio communication, information technology equipment, data processing equipment, audio/video systems, medical electrical equipment, measurement and limitation of radio interference, alarm systems, navigation instruments.
Appendix I. Quick Reference
Abbreviations, model codes and terms used throughout this document.
|
Abbreviation / term |
Meaning |
|
SC |
Three-phase epoxy resin cast dry-type transformer; HV and LV windings wire-wound |
|
SCB / SC(L)B |
As SC, but with a foil-wound LV winding (copper or aluminium foil) |
|
SCZB |
Three-phase epoxy cast dry-type transformer with on-load tap-changing |
|
AN |
Natural air cooling |
|
AF |
Forced-air cooling |
|
Dyn11 |
HV delta, LV star with neutral brought out; 11 o'clock vector position |
|
Yyn0 |
HV star, LV star with neutral brought out; 0 o'clock vector position |
|
Uk |
Short-circuit impedance, in % |
|
LI / AC |
Lightning impulse withstand level / power-frequency withstand level, in kV |
|
Main transformer |
Large-capacity transformer (>= 1000 kVA) used in grids and power stations |
|
Box-type substation |
Compact prefabricated substation (typically 10 - 630 kVA) |